Air-cooled heat exchangers with three tube rows are commonly seen in domestic air-conditioning systems. The analytical solutions of heat exchanger effectiveness for three-row plate fin-and-tube heat exchangers with alternating circuitries have been derived and expressed explicitly in terms of heat capacity ratio and number of transfer units in the recent study. These set of exact solutions serve as a basic tool in designing heat exchanger circuitry to its most accurate possible effectiveness. Comparison of plate-fin-tube heat exchanger effectiveness between airside unmixed and mixed for three-row configurations shows that the effectiveness could be different from 0.3 to 2.4% for the NTUs (Number of Thermal Units) range from 1.0 to 3.0. On the other hand, the result of the comparison of effectiveness between identical and alternating circuiting for 3-row crossflow heat exchangers shows that alternating circuiting could have less effectiveness than identical circuiting from 0.4 to 8.8% in the NTUs range from 1.0 to 3.0. Nevertheless, alternating circuit has its benefit for lower NTU cases, result shows that it could have 1.7 to 0.1% advantages over identical flow arrangement for 2-row heat exchangers with NTUs range from 1.0 to 2.0.
Skip Nav Destination
ASME 2003 Heat Transfer Summer Conference
July 21–23, 2003
Las Vegas, Nevada, USA
Conference Sponsors:
- Heat Transfer Division
ISBN:
0-7918-3693-2
PROCEEDINGS PAPER
Effectiveness of 3-Row Crossflow Heat Exchangers With Alternating Circuitry
Tony D. Chen
Tony D. Chen
James Madison University, Harrisonburg, VA
Search for other works by this author on:
Tony D. Chen
James Madison University, Harrisonburg, VA
Paper No:
HT2003-47104, pp. 229-234; 6 pages
Published Online:
December 17, 2008
Citation
Chen, TD. "Effectiveness of 3-Row Crossflow Heat Exchangers With Alternating Circuitry." Proceedings of the ASME 2003 Heat Transfer Summer Conference. Heat Transfer: Volume 1. Las Vegas, Nevada, USA. July 21–23, 2003. pp. 229-234. ASME. https://doi.org/10.1115/HT2003-47104
Download citation file:
5
Views
0
Citations
Related Proceedings Papers
Related Articles
Performance Analysis of Printed Circuit Heat Exchanger for Supercritical Carbon Dioxide
J. Heat Transfer (June,2017)
Latent Heat Effects in Thermoelectric Air Conditioners and Heat Pumps Equipped With a Heat Exchanger
J. Energy Resour. Technol (September,1996)
The Development of
Performance Prediction Methods for an Automotive CO 2 A/C
Cycle
J. Thermal Sci. Eng. Appl (June,2011)
Related Chapters
Characteristics, Components, and Performance of A/C System Exchangers
Heat Exchanger Engineering Techniques
Siphon Seals and Water Legs
Hydraulics, Pipe Flow, Industrial HVAC & Utility Systems: Mister Mech Mentor, Vol. 1
Hydrodynamic Mass, Natural Frequencies and Mode Shapes
Flow-Induced Vibration Handbook for Nuclear and Process Equipment