Radiant floor heating systems have become popular due to their advantages over conventional heating systems in residential, commercial and industrial spaces. They are also used for snow and ice melting and turf conditioning applications. This paper presents a general study focuses on the design of radiant floor heating systems and investigates the effect of design parameters such as pipe spacing (ranging from 4 in. to 12 in.), pipe depth (ranging from 2.5 in. to 6.5 in.) and pipe temperature (45 °C, 65 °C and 85 °C) on the performance of radiant floor heating system embedded in different mediums (air, gravel and sand). The experimental results showed that a radiant heating system with pipes embedded at a shallow burial depth and placed closer together resulted with a more desired floor temperature distribution. The average floor temperature was also higher when the piping system was embedded in an air-filled space instead of a porous medium such as gravel or sand.